| Sign In | Join Free | My carsrow.com |
|
Brand Name : B&R
Model Number : X20AO4622
Certification : COC
Place of Origin : Austria
MOQ : 1EA
Price : USD
Payment Terms : T/T
Supply Ability : 10EA
Delivery Time : 3-5 DAYS
Packaging Details : Original
Product Name : B&R
Product Model : X20AO4622
Product Type : I/O module
ID code : 0x1BA3
Internal I/O : 1.8 W (Rev. ≥ J0), 2.2 W (Rev. < J0)
Warranty : 1 Year


X20AO4622
X20 analog output module, 4 outputs, 10 V or 0 to 20 mA / 4 to 20 mA, 13-bit converter resolution
| B&R ID code | 0x1BA3 |
| Status indicators | I/O function per channel, operating state, module status |
| Diagnostics | |
| Module run/error | Yes, using LED status indicator and software |
| Channel type | Yes, using software |
| Power consumption | |
| Bus | 0.01 W |
| Internal I/O | 1.8 W (Rev. ≥ J0), 2.2 W (Rev. < J0) |
| Additional power dissipation caused by actuators (resistive) [W] | - |
| Certifications | |
| CE | Yes |
| UKCA | Yes |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| DNV | Temperature: B(0 - 55°C) Humidity: B(up to 100%) Vibration: B(4 g) EMC: B(bridge and open deck) |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| EAC | Yes |
| KC | Yes |
| Output | ±10 V or 0 to 20 mA / 4 to 20 mA, via different terminals |
| Max. output current | 10 mA at voltage >5 V 15 mA at voltage <5 V |
| Digital converter resolution | |
| Voltage | ±12-bit |
| Current | 12-bit |
| Conversion time | 300 µs for all outputs |
| Settling time on output change over entire range | 500 µs |
| Switch on/off behavior | Internal enable relay for startup |
| Max. error | |
| Voltage | |
| Gain | 0.08% |
| Offset | 0.05% |
| Current | |
| Gain | 0.09% |
| Offset | 0.05% |
| Output protection | Short-circuit proof |
| Output format | |
| Voltage | INT 0x8001 - 0x7FFF / 1 LSB = 0x0008 = 2.441 mV |
| Current | INT 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 µA |
| Load per channel | |
| Voltage | Max. ±10 mA, load ≥1 kΩ |
| Current | Load max. 600 Ω (Rev. ≥ J0), 500 Ω (Rev. < J0) |
| Short-circuit proof | Current limiting ±40 mA |
| Output filter | First-order low-pass filter / cutoff frequency 10 kHz |
| Max. gain drift | |
| Voltage | 0.015%/°C |
| Current | 0.02 %/°C |
| Max. offset drift | |
| Voltage | 0.032%/°C |
| Current | 0.032%/°C |
| Error caused by load change | |
| Voltage | Max. 0.11%, from 10 MΩ → 1 kΩ, resistive |
| Current | Max. 0.5%, from 1 Ω → 600 Ω, resistive |
| Nonlinearity | <0.007% |
| Insulation voltage between channel and bus | 500 Veff |
| Electrical isolation | Channel isolated from bus Channel not isolated from channel |
| Mounting orientation | |
| Horizontal | Yes |
| Vertical | Yes |
| Installation elevation above sea level | |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
| Temperature | |
| Operation | |
| Horizontal mounting orientation | -25 to 60°C (Rev. ≥ J0), 0 to 55°C (Rev. < J0) |
| Vertical mounting orientation | -25 to 50°C (Rev. ≥ J0), 0 to 50°C (Rev. < J0) |
| Derating | See section "Derating". |
| Storage | -40 to 85°C |
| Transport | -40 to 85°C |
| Relative humidity | |
| Operation | 5 to 95%, non-condensing |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Note | Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately. |
| Pitch | 12.5+0.2mm |
|
|
X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA Images |